Section 96 of 101
95. Digital Twin Integration
Stable section ID: S05-CON-006-SECTION-96 · 49 content blocks
The Building BIOS and Digital Twin shall maintain a controlled exchange of identity, configuration, state, geometry, and lifecycle information.
The BIOS shall remain authoritative for:
active Configuration Baseline;
registered identities;
permissions;
Interface connection state;
commissioned capabilities;
operating restrictions;
BIOS-managed events;
current authorization.
The Digital Twin may remain authoritative for:
detailed geometric representation;
simulation models;
visualization;
performance analysis;
predictive models;
historical analysis;
engineering scenarios.
The integration shall distinguish:
As-Designed;
As-Manufactured;
As-Installed;
As-Commissioned;
As-Operated;
As-Maintained;
As-Modified;
As-Decommissioned.
Data exchanged may include:
Component and Cartridge identities;
locations and coordinate transformations;
Interface relationships;
capabilities;
state and health;
faults;
maintenance history;
sensor data references;
configuration versions;
simulation results;
- predicted degradation.
- Digital Twin predictions shall not overwrite BIOS-observed or verified states.
A discrepancy shall create a reconciliation record identifying:
BIOS value;
Digital Twin value;
source;
authority;
confidence;
required verification;
proposed resolution.