Section 24 of 101
23. Time, Location & Context Services
Stable section ID: S05-CON-006-SECTION-24 · 35 content blocks
The BIOS shall provide authoritative time, location, and operational context to components and higher-level services.
The Time Service shall provide:
current time;
timezone;
synchronization status;
time source;
accuracy estimate;
monotonic sequence reference;
daylight-saving handling where applicable.
A loss or correction of wall-clock time shall not reverse event ordering. Safety-critical durations shall use monotonic time sources where possible.
The Location Service shall maintain hierarchical building locations such as:
site;
building;
level;
zone;
room;
structural grid;
Node;
Interface;
- Cartridge position.
- Location shall distinguish designed position from verified installed position.
The Context Service may represent:
normal occupancy;
unoccupied condition;
construction;
commissioning;
maintenance;
emergency;
fire response;
power outage;
network isolation;
severe weather;
- partial building shutdown.
- Context shall affect permissions and operating policies only through approved rules.
Location and context data derived from inference shall be identified as inferred. Privacy-sensitive occupant context shall be minimized, protected, and separated from basic engineering configuration where possible.