Section 66 of 101
65. Health Monitoring
Stable section ID: S05-CON-006-SECTION-66 · 47 content blocks
Health Monitoring determines whether BIOS hardware, services, components, Cartridges, Interfaces, communication networks, storage, and dependencies remain capable of performing their required functions.
Health status shall be represented as:
healthy;
healthy with advisory;
degraded;
maintenance required;
critical;
unavailable;
unknown.
Health Monitoring may evaluate:
service availability;
communication quality;
storage integrity;
processor and memory condition;
power quality;
backup readiness;
sensor validity;
actuator response;
Interface state;
temperature;
vibration;
leakage;
corrosion;
cycle count;
calibration status;
inspection status;
software support;
cybersecurity status.
A Health Record shall include:
subject identity;
health state;
contributing indicators;
thresholds;
data source;
confidence;
trend;
time of assessment;
required action.
Health shall not be inferred solely from communication availability. A connected device may be physically failed, and a passive component may remain healthy without digital communication.
The BIOS shall distinguish among:
current failure;
degradation trend;
overdue inspection;
expired evidence;
loss of observability;
- actual loss of function.
- Loss of monitoring shall create an Unknown or Unverified health state rather than a false Healthy state.